1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: JW DIDADO ELECTRIC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of JW DIDADO ELECTRIC in 825 TECH CENTER DRIVE, GAHANNA, OH 43230 (NAICS 221122). OSHA activity number 348820556.

Establishment
JW DIDADO ELECTRIC
Site address
825 TECH CENTER DRIVE
City
GAHANNA
State
OH
ZIP
43230
Mailing
1033 KELLY AVENUE, AKRON, OH 44306
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
1183
Ownership type
A

1 citation on file for this inspection.

1926.416 A01

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4823 · Current $0 Reduced
29 CFR  1926.416(a)(1): No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.  a. On or about March 17, 2025 and times prior located at 825 Tech Center Drive, Gahanna, Ohio, 43230: The employer did not ensure that their employees were protected from energized electrical circuits. Employees were tasked with installing lockout/tagout devices within live 120/208-volt electrical panels. The panels had open breaker spaces, which exposed live busbars, presenting an electric shock hazard to the employees.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4823

PSE&G