Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MUSGROVE CONSTRUCTION INC

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of MUSGROVE CONSTRUCTION INC in HIGHWAY 18, FORT WHITE, FL 32062 (NAICS 000000). OSHA activity number 110140357.

Watch Musgrove Construction INC — free Get an email when a new federal OSHA severe-injury report for Musgrove Construction INC is published. One employer, no account, unsubscribe in one click.
Site address
HIGHWAY 18
City
FORT WHITE
State
FL
ZIP
32062
Mailing
8708 US 90, LIVE OAK, FL 32060
Inspection type
Accident-driven (A)
Scope
Complete (A)
Discipline
Safety
Advance notice
Yes
Union status
N
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
1731
Employees
20
Ownership type
A

8 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4200.00 · Current $2940.00 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did
not furnish employment and a place of employment which were free from
recognized
hazards that were causing or likely to cause death or serious physical
harm to employees
in that employees were exposed to hazards of electrocution:
a.Along highway 464B, employees were replacing 14,400-volt lightning
arresters with 7,200-volt lightning arresters on Blichton feeder lines four
and five, consisting of three 7,200 volts phases each, had not ensured that
the automatic-reclosing devices were tagged or made inoperative. This
violation occurred on or about March 12, 1997.
Among other methods, one feasible and acceptable abatement method to
correct this
hazard is to ensure that the automatic reclosure devices have been made
inoperative.
Permits and tags must be installed on the oil circuit reclosurer or other
circuit devices
where work is being done on energized parts.
IN THE ALTERNATIVE
29 CFR 1926.417(a):  Controls that were to be deactivated during the
course of work on
energized or deenergized equipment or circuits were not tagged:
a.Along highway 464B, employees were replacing 14,400-volt lightning
arresters with 7,200-volt lightning arresters on Blichton feeder lines four
and five, consisting of three 7,200 volts phases each, had not ensured that
the automatic-reclosing devices were tagged or made inoperative. This
violation occurred on or about March 12, 1997.
ABATEMENT VERIFICATION IS REQUIRED
Recent events (2)
  • — I (S) $2940.00
  • — Z (S) $4200.00

1926.21 B02

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by

1926.950 E01 I

Serious Gravity 10 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $2940.00 · Current $2940.00

1926.95 A

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2940.00 · Current $2940.00

1926.950 C01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by

1926.454 A

Serious Gravity 10 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $2940.00 · Current $2940.00

1926.955 A06 I

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $2940.00 · Current $2940.00

1926.955 A06 II

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $2940.00 · Current $2940.00

View MUSGROVE CONSTRUCTION INC's full OSHA safety record →