Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: EAST COAST REPAIR AND FABRICATION

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of EAST COAST REPAIR AND FABRICATION in 3400 SHIPWRIGHT STREET, PORTSMOUTH, VA 23703 (NAICS 811219). OSHA activity number 338481633.

Watch East Coast Repair AND Fabrication — free Get an email when a new federal OSHA severe-injury report for East Coast Repair AND Fabrication is published. One employer, no account, unsubscribe in one click.
Site address
3400 SHIPWRIGHT STREET
City
PORTSMOUTH
State
VA
ZIP
23703
Mailing
5803 CURLEW DRIVE, NORFOLK, VA 23502
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811219
Employees
177
Ownership type
A

9 citations on file for this inspection.

1910.242 B

Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.242(b):     Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:    a.)  East Coast Repair and Fabrication, Maintenance Shop:  On or about 01/15/13, employees were using compressed air to clean tools and parts at greater than 100 p.s.i., creating a physical hazard.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.253 B04 III

Serious Gravity 5 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.253(b)(4)(iii):     Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.    a.)  East Coast Repair and Fabrication, between Maintenance Shop and Pipe Shop:  On or about 01/15/13 oxygen cylinders were stored next to fuel gas cylinders and not separated by a minimum distance of 20 feet or by a noncombustible barrier at least 5 feet high having a fire-resistance rating of at least one-half hour, creating a fire hazard.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.253 E05 IV

Serious Gravity 5 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.253(e)(5)(iv):     Hose connections were not clamped or otherwise securely fastened in a manner that would withstand, without leakage, twice the pressure to which they would normally be subjected in service, but in no case less than a pressure of 300 p.s.i.:    a.)  East Coast Repair and Fabrication, Maintenance Shop:  On or about 01/15/13, employees were using burning hoses with repairs that were not pressure tested to 300 p.s.i., creating a fire hazard.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.303(g)(2)(i):     Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    a.)  East Coast Repair and Fabrication, Electricians Room:  On or about 01/17/13, openings in a 220 volt panel box exposed live parts of electrical equipment, creating a contact with electrical current hazard.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.305 B01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4500.00 · Current $2700.00 Reduced
29 CFR 1910.305(b)(1)(i):     Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:    a.)  East Coast Repair and Fabrication, Electricians Room:  On or about 01/17/13, conductors of two portable heaters were not protected from abrasion while being hard wired into a panel box, creating a contact with electrical current hazard.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4500

1910.305 G01 III

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iii):     Flexible cords used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of 29 CFR 1910.305 were not equipped with an attachment plug and energized from an approved receptacle outlet:    a.)  East Coast Repair and Fabrication, Electricians Room:  On or about 01/17/13, the employer had two portable heaters hard wired into a circuit breaker, creating a contact with electrical current hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 F02

Other-than-serious 1 instance 25 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(f)(2):     Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:      a.)  East Coast Repair and Fabrication, Machine Shop:  On or about 01/17/13, the panel box supplying power to welding machines, press brake, outlets, and lights was not labeled, creating a failure to warn or secure hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1001 J02 III

Other-than-serious 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1001(j)(2)(iii):     The building owner or facility owner did not inform employers of employees who performed housekeeping activities of the presence and location of asbestos containing material (ACM) or presumed asbestos containing material (PACM) in such areas that may be contacted during such activities:      a.)  East Coast Repair and Fabrication, Pipe Shop and Machine Shop:  On or about 01/15/13, the employer did not inform employees conducting housekeeping activities that the TSI around a pipe contained asbestos, creating a contact with toxic substance hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1001 J05 I

Other-than-serious 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1001(j)(5)(i):     The employer did not affix signs or labels so that employees would be notified of what materials contain ACM and/or PACM to materials that were previously identified to be ACM and/or PACM:    a.)  East Coast Repair and Fabrication, Pipe Shop and Machine Shop:  On or about 01/15/13, asbestos pipe insulation was not labeled, creating a contact with toxic substance hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View EAST COAST REPAIR AND FABRICATION's full OSHA safety record →

ACES, LLC

DACS INC

VAFMC LLC

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338481633.