Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: EXECUTIVE COACH BUILDERS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of EXECUTIVE COACH BUILDERS in 4400 W. PRODUCTION ST., SPRINGFIELD, MO 65803 (NAICS 336211). OSHA activity number 340108075.

Watch Executive Coach Builders — free Get an email when a new federal OSHA severe-injury report for Executive Coach Builders is published. One employer, no account, unsubscribe in one click.
Site address
4400 W. PRODUCTION ST.
City
SPRINGFIELD
State
MO
ZIP
65803
Mailing
4400 W. PRODUCTION ST., SPRINGFIELD, MO 65803
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336211
Employees
85
Ownership type
A

3 citations on file for this inspection.

1910.219 C04 II

Other-than-serious 1 instance 1 exposed
Issued
Penalty
Initial $2800.00 · Current $900.00 Reduced
29 CFR 1910.219(c)(4)(ii): The unused keyway(s) of projecting shaft end(s) were not filled up or covered:      On or about January 27, 2015 at the Executive Coach Builders facility- Employees were exposed to a air compressor that had a projecting keyway that was not covered or guarded.     Abatement certification for this violation is not required.
Recent events (2)
  • — I (O) $900
  • — Z (S) $2800

1910.303 B02

Serious Gravity 5 30 instances 80 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1400.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   On or about January 27, 2015 at the Executive Coach Builders Facility- employees were exposed to serious injuries due to electrical Shock  in that a couple dozen Metal Junction Boxes that was listed and labeled for permanent mounting only, was being used in junction with an extension cords.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1910.304 G05

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $2800.00 · Current $1400.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective:   On or about January 27, 2015 at the Executive Coach Builders Facility, employees were exposed to Electrical Shock injuries, in that the cord on a 30 inch industrial fan in use did not have a ground pin to ensure the path to ground was permanent, continuous and effective.               Abatement certification is not required for this item.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

View EXECUTIVE COACH BUILDERS's full OSHA safety record →