1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: LINDEN LUMBER COMPANY

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of LINDEN LUMBER COMPANY in 23741 US HWY 43, LINDEN, AL 36748 (NAICS 321113). OSHA activity number 340653534.

Watch Linden Lumber Company — free Get an email when a new federal OSHA severe-injury report for Linden Lumber Company is published. One employer, no account, unsubscribe in one click.
Site address
23741 US HWY 43
City
LINDEN
State
AL
ZIP
36748
Mailing
23741 US HWY 43, LINDEN, AL 36748
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321113
Employees
240
Ownership type
A

4 citations on file for this inspection.

1910.147 C04 II B

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $4950.00 · Current $2970.00 Reduced
29 CFR 1910.147(c)(4)(ii)(B): The energy control procedure did not clearly and specifically specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy:  a)  Head rig and Carriage;  On or about May 20, 2015 and at times prior thereto, the employer exposed employees to hazardous energies in that the machine specific procedure did not specify procedural steps to control the hydraulic and pneumatic energies when employees are performing maintenance on the head rig and carriage.
Recent events (2)
  • — I (S) $2970
  • — Z (S) $4950

1910.303 F02

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $4208.00 · Current $2250.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a)  Disconnect for Head rig;  On or about May 20, 2015 and at times prior thereto, the employer exposed employees to electrical hazards in that the 480 VAC main disconnect for the head rig was not labeled to indicate its purpose, nor was it arranged so the purpose was evident.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $4208

1910.305 G01 IV A

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2525.00 · Current $1780.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a)  Sawmill above the Edger;  On or about May 20, 2015 and at times prior thereto, the employer exposed employees to electrical hazards in that employees were allowed to walk and work around a temporary flexible cord used to power a fan that had been used in lieu of fixed wiring.
Recent events (2)
  • — I (S) $1780
  • — Z (S) $2525

1910.305 G01 IV D

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces:  a)  Sawmill above the Edger;  On or about May 20, 2015 and at times prior thereto, the employer exposed employees to electrical hazards in that employees were allowed to walk and work around a flexible cord that was attached to the trusses in the ceiling.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View LINDEN LUMBER COMPANY's full OSHA safety record →