POSTON, AZ —
OSHA Inspection: BIA/WESTERN REGION/COLORADO RIVER AGENCY
Follow-up inspection · Health discipline
At a glance
On , OSHA opened a follow-up health inspection of BIA/WESTERN REGION/COLORADO RIVER AGENCY in IRRIGATION MAINTENANCE 21051-3 EAST POSTON ROAD, POSTON, AZ 85371 (NAICS 921190). OSHA activity number 342399755.
Where did this inspection happen?
- Establishment
- BIA/WESTERN REGION/COLORADO RIVER AGENCY
- Site address
- IRRIGATION MAINTENANCE 21051-3 EAST POSTON ROAD
- City
- POSTON
- State
- AZ
- ZIP
- 85371
- Mailing
- 12124 1ST AVENUE, PARKER, AZ 85344
What kind of inspection was it?
- Inspection type
- Follow-up (F)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 921190
- Employees
- 83
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Maintenance Shop, Poston, AZ: Employees were using a Porta Cool unit plugged into a series-connected extension cord and relocatable power tap (RPT). Per UL listing, RPTs are not to be series-connected to other RPTs or connected to extension cords. Employees were exposed to a potential fire hazard.
Recent events (1)
- — Z (S) $0
1910.304 A02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity: Outside wall of the Maintenance Shop Office: The duplex receptacle supplying power to the Porta Cool unit was wired with reverse polarity. Employees were exposed to an electrical shock hazard.
Recent events (1)
- — Z (S) $0
1910.334 A02 I
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): Maintenance Shop, Poston, AZ: The 100-foot yellow extension cord used to power the Porta Cool unit had a damaged outer jacket which exposed the inner conductors. Employees were exposed to a potential electrical shock hazard.
Recent events (1)
- — Z (S) $0
More inspections at BIA/WESTERN REGION/COLORADO RIVER AGENCY
PARKER, AZ—2022-10-05 00:00:00
BIA/WESTERN REGION/COLORADO RIVER AGENCY
POSTON, AZ—2017-09-15 00:00:00
BIA/WESTERN REGION/COLORADO RIVER AGENCY
POSTON, AZ—2017-06-14 00:00:00
BIA/WESTERN REGION/COLORADO RIVER AGENCY
POSTON, AZ—2017-06-14 00:00:00
BIA/WESTERN REGION/COLORADO RIVER AGENCY
POSTON, AZ—2017-01-05 00:00:00
BIA/WESTERN REGION/COLORADO RIVER AGENCY
View BIA/WESTERN REGION/COLORADO RIVER AGENCY's full OSHA safety record →
More inspections in this industry (NAICS 921190)
TOPSHAM, VT—2026-07-09
TOPSHAM, TOWN OF
SPRINGFIELD, IL—2026-07-07
IL DEPT. OF AGRICULTURE - AGRICULTURAL PRODUCTS INSPECTION LABORATORY
MAYVILLE, NY—2026-07-07
MAYVILLE VILLAGE HALL
BOQUERON, PR—2026-07-07
MUNICIPIO DE CABO ROJO
ROCHESTER, NY—2026-07-06
IRONDEQUOIT TOWN HALL
More inspections in AZ
CHANDLER, AZ—2026-07-16
SUN STATE BUILDERS
CHANDLER, AZ—2026-07-16
PREMIER UNDERGROUND CONSTRUCTION LLC
CAMP VERDE, AZ—2026-07-14
CLIFF CASTLE CASINO & HOTEL
CAMP VERDE, AZ—2026-07-14
CLIFF CASTLE CASINO & HOTEL
TUCSON, AZ—2026-07-10
CPX2026XJL680X0074 - JANC EXCAVATING AND CONSTRUCTION, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342399755.