COCOA, FL —
OSHA Inspection: BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC. in 550 CIDCO ROAD, COCOA, FL 32926 (NAICS 238990). OSHA activity number 343470530.
Where did this inspection happen?
- Site address
- 550 CIDCO ROAD
- City
- COCOA
- State
- FL
- ZIP
- 32926
- Mailing
- 550 CIDCO RD., COCOA, FL 32926
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238990
- Employees
- 397
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.212 A03 II
- Issued
- Abate by
- Penalty
- Initial $13260.00 · Current $12151.00 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): a. On or about 9/18/2018, at the jobsite, the Lodge & Shipley Power Press Brake #S-18 & the Red Hydraulic Press did not have guards to protect employees from amputation hazards.
Recent events (3)
- — J (O) $12151
- — C (S) $13260
- — Z (S) $13260
1910.303 G01 I
- Issued
- Abate by
- Penalty
- Initial $7577.00 · Current $6944.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: a. On or about 9/18/2018, at the jobsite, a rack of welding cables were stored 16 inches from the face of the 220 volt electrical panels along the east wall.
Recent events (3)
- — J (O) $6944
- — C (S) $7577
- — Z (S) $7577
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $8680.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a. On or about 9/18/2018, at the jobsite, breaker panel B along the east wall was missing a breaker and there was no filler panel in place.
Recent events (3)
- — J (O) $8680
- — C (S) $9472
- — Z (S) $9472
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. On or about 9/18/2018, at the jobsite, the breakers in the electrical panels along the east wall were not marked in a manner to identify the purpose of the breakers.
Recent events (3)
- — J (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC.
CLEARWATER, FL—2023-12-19 00:00:00
BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC.
TAMPA, FL—2021-01-29 00:00:00
BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC.
ORLANDO, FL—2018-09-05 00:00:00
BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC.
SAINT AUGUSTINE, FL—2018-06-05 00:00:00
BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC.
JACKSONVILLE, FL—2015-01-09 00:00:00
BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC.
View BEYEL BROTHERS CRANE AND RIGGING OF SOUTH FLORIDA, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238990)
NEW YORK, NY—2026-07-09
PALM INDUSTRIES LLC
NEW YORK, NY—2026-07-09
PALM INDUSTRIES LLC
EL PASO, TX—2026-07-09
RM CRANE & RIGGING LLC.
LAKEWOOD, WA—2026-07-08
WA317992018 - HARMON INC DBA HARMON SERVICE GLAZING INC
VICTOR, NY—2026-07-08
DIMARCO CONSTRUCTORS
More inspections in FL
MARIANNA, FL—2026-07-13
PRIMETIME MOBILE MASONRY LLC
MELBOURNE, FL—2026-07-13
OMNIPOTENT BRANDS, LLC
QUINCY, FL—2026-07-13
WALMART
INDIAN ROCKS BEACH, FL—2026-07-10
UNKNOWN CONTRACTOR
CLEARWATER, FL—2026-07-10
ROOFTECH ROOFING & WATERPROOFING INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343470530.