OSHA Inspection: GULFSTREAM AEROSPACE SERVICES CORPORATION

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of GULFSTREAM AEROSPACE SERVICES CORPORATION in W6365 DISCOVERY DR., APPLETON, WI 54914 (NAICS 488190). OSHA activity number 346076730.

Watch Gulfstream Aerospace Services Corporation — free Get an email when a new federal OSHA severe-injury report for Gulfstream Aerospace Services Corporation is published. One employer, no account, unsubscribe in one click.
Site address
W6365 DISCOVERY DR.
City
APPLETON
State
WI
ZIP
54914
Mailing
W6365 DISCOVERY DR., APPLETON, WI 54914
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488190
Employees
1006
Ownership type
A

4 citations on file for this inspection.

1910.107 B05 IV

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $8806.00 · Current $5284.00 Reduced
29 CFR  1910.107(b)(5)(iv):  Space within the spray booth on the downstream and upstream sides of filters shall be protected with approved automatic sprinklers:  At a facility located at W6365 Discovery Drive, Appleton, WI 54914; the employer did not protect the downstream and upstream sides of filters in the Upholstery spray booth with approved automatic sprinklers. Employees were engaged in spray application of flammable adhesives in the spray booth; automatic fire protection was not provided on either side of the spray booth's filters.
Recent events (2)
  • — I (S) $5283.6
  • — Z (S) $8806

1910.107 B09

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.107(b)(9):  Spray booths shall be so installed that all portions are readily accessible for cleaning. A clear space of not less than 3 feet on all sides shall be kept free from storage or combustible construction:  At a facility located at W6365 Discovery Drive, Appleton, WI 54914; the Upholstery spray booth was not installed so that a clear space of not less than 3 feet on all sides was kept free from storage or combustible construction. Storage along the sides of the booth, such as a flammable cabinet and steel racking, did not keep a clear space of 3 feet along the sides of the spray booth. Combustible construction, such as foam insulation pieces, were located on the top of the booth around the ductwork for the booth's ventilation system.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7044.00 · Current $4226.00 Reduced
29 CFR 1910.303(b)(2):  Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:  At a facility located at W6365 Discovery Drive, Appleton, WI 54914; metallic outlet boxes (handy box) were connected to flexible cords and used as suspended pendant outlets throughout the Upholstery shop. A pendant outlet near the Upholstery spray booth was used to power outlets in a work bench which were used to power a heat gun. The metal outlet boxes were not installed in accordance with the UL identifier QCIT, which states that boxes shall be mounted in or on a surface.
Recent events (2)
  • — I (S) $4226.4
  • — Z (S) $7044

1910.107 B05 I

Deleted Other-than-serious 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.107(b)(5)(i):  The spraying operations except electrostatic spraying operations shall be so designed, installed and maintained that the average air velocity over the open face of the booth (or booth cross section during spraying operations) shall be not less than 100 linear feet per minute. Visible gauges or audible alarm or pressure activated devices shall be installed to indicate or insure that the required air velocity is maintained:  At a facility located at W6365 Discovery Drive, Appleton, WI 54914; the employer did not maintain an average air velocity of 100 linear feet per minute (fpm) over the open face of the Upholstery department's spray booth. The air velocity over the open face of the Upholstery department's spray booth, used in part for the spray application of flammable adhesives, averaged approximately 62 fpm.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View GULFSTREAM AEROSPACE SERVICES CORPORATION's full OSHA safety record →