APPLETON, WI —
OSHA Inspection: GULFSTREAM AEROSPACE SERVICES CORPORATION
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of GULFSTREAM AEROSPACE SERVICES CORPORATION in W6365 DISCOVERY DR., APPLETON, WI 54914 (NAICS 488190). OSHA activity number 346076730.
Where did this inspection happen?
- Establishment
- GULFSTREAM AEROSPACE SERVICES CORPORATION
- Site address
- W6365 DISCOVERY DR.
- City
- APPLETON
- State
- WI
- ZIP
- 54914
- Mailing
- W6365 DISCOVERY DR., APPLETON, WI 54914
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 488190
- Employees
- 1006
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.107 B05 IV
- Issued
- Abate by
- Penalty
- Initial $8806.00 · Current $5284.00 Reduced
General-duty citation text
29 CFR 1910.107(b)(5)(iv): Space within the spray booth on the downstream and upstream sides of filters shall be protected with approved automatic sprinklers: At a facility located at W6365 Discovery Drive, Appleton, WI 54914; the employer did not protect the downstream and upstream sides of filters in the Upholstery spray booth with approved automatic sprinklers. Employees were engaged in spray application of flammable adhesives in the spray booth; automatic fire protection was not provided on either side of the spray booth's filters.
Recent events (2)
- — I (S) $5283.6
- — Z (S) $8806
1910.107 B09
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.107(b)(9): Spray booths shall be so installed that all portions are readily accessible for cleaning. A clear space of not less than 3 feet on all sides shall be kept free from storage or combustible construction: At a facility located at W6365 Discovery Drive, Appleton, WI 54914; the Upholstery spray booth was not installed so that a clear space of not less than 3 feet on all sides was kept free from storage or combustible construction. Storage along the sides of the booth, such as a flammable cabinet and steel racking, did not keep a clear space of 3 feet along the sides of the spray booth. Combustible construction, such as foam insulation pieces, were located on the top of the booth around the ductwork for the booth's ventilation system.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $7044.00 · Current $4226.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling: At a facility located at W6365 Discovery Drive, Appleton, WI 54914; metallic outlet boxes (handy box) were connected to flexible cords and used as suspended pendant outlets throughout the Upholstery shop. A pendant outlet near the Upholstery spray booth was used to power outlets in a work bench which were used to power a heat gun. The metal outlet boxes were not installed in accordance with the UL identifier QCIT, which states that boxes shall be mounted in or on a surface.
Recent events (2)
- — I (S) $4226.4
- — Z (S) $7044
1910.107 B05 I
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.107(b)(5)(i): The spraying operations except electrostatic spraying operations shall be so designed, installed and maintained that the average air velocity over the open face of the booth (or booth cross section during spraying operations) shall be not less than 100 linear feet per minute. Visible gauges or audible alarm or pressure activated devices shall be installed to indicate or insure that the required air velocity is maintained: At a facility located at W6365 Discovery Drive, Appleton, WI 54914; the employer did not maintain an average air velocity of 100 linear feet per minute (fpm) over the open face of the Upholstery department's spray booth. The air velocity over the open face of the Upholstery department's spray booth, used in part for the spray application of flammable adhesives, averaged approximately 62 fpm.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at GULFSTREAM AEROSPACE SERVICES CORPORATION
APPLETON, WI—2019-04-10 00:00:00
GULFSTREAM AEROSPACE SERVICES CORPORATION
CAHOKIA, IL—2018-01-19 00:00:00
GULFSTREAM AEROSPACE SERVICES CORPORATION
View GULFSTREAM AEROSPACE SERVICES CORPORATION's full OSHA safety record →
More inspections in this industry (NAICS 488190)
VANDALIA, OH—2026-07-08
SIERRA NEVADA CORPORATION
ASPEN, CO—2026-06-17
ATLANTIC AVIATION-MONTROSE LLC
GULF SHORES, AL—2026-06-17
TREGO/DUGAN AVIATION OF GRAND ISLAND, INC.
LOS ANGELES, CA—2026-06-12
UNITED AIRLINES
DORAL, FL—2026-05-28
FLIGHT POWER REPAIR GROUP, LLC
More inspections in WI
MUSCODA, WI—2026-07-10
SCOT INDUSTRIES, INC
FRANKLIN, WI—2026-07-10
EDGE BROADBAND SOLUTIONS LLC
APPLETON, WI—2026-07-10
LAWRENCE UNIVERSITY OF WISCONSIN
KIMBERLY, WI—2026-07-10
ENRIQUE RESENDIC
SLINGER, WI—2026-07-10
DYLAN MATTHEW SHELLEY LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346076730.