ABBOTSFORD, WI —
OSHA Inspection: PACKERS SANITATION SERVICES INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of PACKERS SANITATION SERVICES INC. in 502 E LINDEN ST., ABBOTSFORD, WI 54405 (NAICS 561720). OSHA activity number 347941825.
Where did this inspection happen?
- Establishment
- PACKERS SANITATION SERVICES INC.
- Site address
- 502 E LINDEN ST.
- City
- ABBOTSFORD
- State
- WI
- ZIP
- 54405
- Mailing
- 1050 CROWN POINT PARKWAY, DUNWOODY, GA 30338
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561720
- Employees
- 60
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.147 C04 II B
- Issued
- Abate by
- Penalty
- Initial $13005.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(B): Energy control procedures shall clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy: On or about December 18, 2025, at a facility located at 502 E Linden Street in Abbotsford, WI; the employer's energy control procedure titled, "Equipment-Specific Lockout/Tagout Procedure for Sanitation" for the Oven Room 2 Spiral Oven did not clearly and specifically address: a) The specific procedural steps addressing the thermal (heat) energy source by implementing a waiting period or other methods to allow components to cool down prior to sanitation, maintenance, and/or servicing activities. b) The specific procedural steps for shutting down, isolating, and securing either the manual gas valve and/or the Siemens gas valve controlled by the computer system utilized by employees during the sanitation, maintenance, and/or servicing activities. c) The specific procedural steps for shutting down, isolating, and securing the steam energy isolating devices utilized by employees during the sanitation, maintenance, and/or servicing activities.
Recent events (3)
- — F (S) $0
- — C (S) $13005
- — Z (S) $13005
1910.147 C04 II D
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(D): Energy control procedures shall clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, specific requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures: On or about December 18, 2025, at a facility located at 502 E Linden Street in Abbotsford, WI; the employer's energy control procedure titled, "Equipment-Specific Lockout/Tagout Procedure for Sanitation" did not clearly and specifically outline specific requirements for testing and/or verification of the effectiveness of lock devices and other energy control measures for the Oven Room 2 Spiral Oven. The energy control procedure did not contain specific requirements for: a) The administrative controls for the safe dissipation of heat from the oven. b) Testing and verification of the effectiveness of the lockout of the natural gas energy to the equipment. c) Testing and verification of the effectiveness of the lockout of the steam energy to the equipment.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling: On or about December 18, 2025, at a facility located at 502 E Linden Street in Abbotsford, WI; a metallic outlet box (handy box), in the Training Room/Manager's Office, was connected to flexible cords and used as extension cord for computer/equipment charging cords. The metal outlet boxes were not installed in accordance with the UL identifier QCIT, which states that boxes shall be mounted in or on a surface.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at PACKERS SANITATION SERVICES INC.
COLUMBUS JUNCTION, IA—2024-06-03 00:00:00
PACKERS SANITATION SERVICES, INC.
ABBOTSFORD, WI—2023-03-15 00:00:00
PACKERS SANITATION SERVICES, INC.
GRAND ISLAND, NE—2022-11-16 00:00:00
PACKERS SANITATION SERVICES, INC.
COLUMBUS JUNCTION, IA—2022-10-31 00:00:00
PACKERS SANITATION SERVICES, INC.
GREEN BAY, WI—2022-09-22 00:00:00
PACKERS SANITATION SERVICES INC.
View PACKERS SANITATION SERVICES INC.'s full OSHA safety record →
More inspections in this industry (NAICS 561720)
PALM BAY, FL—2026-07-10
ASCEND BUILDING SERVICES, LLC
NOLENSVILLE, TN—2026-07-08
BUSY BS RESIDENTIAL CLEANING COMPANY
TACOMA, WA—2026-07-07
WA317991946 - COASTAL BUSINESS SERVICES GROUP INC
POULSBO, WA—2026-07-07
WA317991849 - SIMPLY HOUSE CLEANING LLC
DIXON, CA—2026-07-07
SANITATION PROCESS CONTROL, LLC
More inspections in WI
MUSCODA, WI—2026-07-10
SCOT INDUSTRIES, INC