2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: EVANS INDUSTRIES INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of EVANS INDUSTRIES INC. in 1841 LEMOYNE AVENUE, SYRACUSE, NY 13208 (NAICS 331524). OSHA activity number 339904658.

Watch Evans Industries INC. — free Get an email when a new federal OSHA severe-injury report for Evans Industries INC. is published. One employer, no account, unsubscribe in one click.
Site address
1841 LEMOYNE AVENUE
City
SYRACUSE
State
NY
ZIP
13208
Mailing
1841 LEMOYNE AVENUE, SYRACUSE, NY 13208
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331524
Employees
43
Ownership type
A

3 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2975.00 · Current $2083.00 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition.        a) In the Grinding Area, on or about 8/13/14: Horizontal surfaces including lighting fixtures, electrical panels, ceilings rafters, pipes, and the floor of a mezzanine level storage area were not kept clean from the accumulation of explosive aluminum dust.         Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $2082.5
  • — Z (S) $2975

1910.307 C

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:      a) In the grinding area, on or about 8/25/14: Where Class II explosive aluminum dust was present throughout the area, electrical equipment including but not limited to electrical panels, motors for ventilation, and pieces of equipment were not rated for a Class II area.        Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.23 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $2975.00 · Current $2083.00 Reduced
29 CFR 1910.23(b)(1): Every wall opening from which there was a drop of more than 4 feet was not guarded.          a) In the upper pattern storage area, on or about 8/13/14: A wall opening used to transfer pattern pieces from the upstairs storage area to the ground level production area was not guarded when actual transfer of pieces was occurring. Employees were exposed to a fall of 10 feet.
Recent events (2)
  • — I (S) $2082.5
  • — Z (S) $2975

View EVANS INDUSTRIES INC.'s full OSHA safety record →