OSHA Inspection: CVR COMMON SERVICES, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CVR COMMON SERVICES, LLC in 906 S. POWELL, WYNNEWOOD, OK 73098 (NAICS 324110). OSHA activity number 347584153.

Watch CVR Common Services, LLC — free Get an email when a new federal OSHA severe-injury report for CVR Common Services, LLC is published. One employer, no account, unsubscribe in one click.
Site address
906 S. POWELL
City
WYNNEWOOD
State
OK
ZIP
73098
Mailing
906 S. POWELL AVE., WYNNEWOOD, OK 73098
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
324110
Employees
325
Ownership type
A

5 citations on file for this inspection.

1910.28 B01 I A

Other-than-serious Gravity 10 2 instances 4 exposed
Issued
Penalty
Initial $16131.00 · Current $12000.00 Reduced
29 CFR  1910.28(b)(1)(i)(A): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level was protected from falling by a standard guardrail system.   On or about June 25, 2024 and at times prior thereto, near 22-2P-253 A/B LCO pumps in FCCU 22 Unit, employees access the first level of two platforms along the corridor that were more than four(4) feet in height and the walking-working surface did not have a complete guardrail system installed.
Recent events (2)
  • — I (O) $12000
  • — Z (S) $16131

1910.37 A03

Other-than-serious Gravity 10 1 instance 4 exposed
Issued
Penalty
Initial $16131.00 · Current $12000.00 Reduced
29 CFR  1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    On or about June 25, 2024, the employer did not ensure the south exit at the Crude 32 Unit Old Control Room was free and unobstructed from the outside. The old control room was being used to store lockers and harnesses, etc. for operators. This working condition exposed employees to potential fire and smoke hazards in the event of fire emergency.
Recent events (2)
  • — I (O) $12000
  • — Z (S) $16131

1910.119 D03 II

Other-than-serious Gravity 10 2 instances 8 exposed
Issued
Penalty
Initial $16131.00 · Current $8000.00 Reduced
29 CFR  1910.119(d)(3)(ii): The employer  did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP).   On or about June 25, 2024, the employer did not ensure that the nameplate on pressure vessels was visible as required by their adopted RAGAGEP ASME Boiler and Pressure Vessel Code Section VIII Division 1 (1968 Edition) Part UG-116 (a) for nameplate per UG-116 (i) for required marking: All required markings shall be located in a conspicuous place on the vessel, preferably near a manhole or handhole.  This condition exposed employees to chemical release hazards for the following equipment: a) Crude Unit  Desalter (32-CD2) b) FCC Unit Hot Oil Surge Drum (22-D201)
Recent events (2)
  • — I (O) $8000
  • — Z (S) $16131

1910.119 E05

Other-than-serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $16131.00 · Current $12000.00 Reduced
29 CFR  1910.119(e)(5): The employer did not establish a system to promptly address the team's findings and recommendations; assure that the recommendations are resolved in a timely manner and that the resolution is documented; document what actions are to be taken; complete actions as soon as possible; develop a written schedule of when these actions are to be completed; communicate the actions to operating, maintenance and other employees whose work assignments are in the process and who may be affected by the recommendations or actions.   On or about June 25, 2024, the employer did not either resolve or document resolution, and or interim measures that were completed, in a timely manner for the 2018 PHA team?s finding and recommendation for Debutanizer Tower 22-3V103.
Recent events (2)
  • — I (O) $12000
  • — Z (S) $16131

1910.119 J05

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $11524.00 · Current $0.00 Reduced
29 CFR  1910.119(j)(5): Equipment deficiencies. The employer did not correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation.   On or about June 25, 2024, the employer did not correct deficiencies in equipment including but not limited to damaged pedestal support foundation with exposed rebar for pressure vessels such as Crude 32 Unit CE-203 (Napoleum 600 Crude Exchanger). This condition exposed employees to chemical release hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $11524

View CVR COMMON SERVICES, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347584153.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.